
Carbon Monoxide Analyst Protocol
INTRODUCTION
The Carbon Monoxide standards and best practices
outlined in this document are designed to provide a protocol for those building
technicians and investigators attempting to determine whether potential exists
for CO to enter a house. This may be in preventative cases, where a homeowner
is concerned about the dangers of CO, or in reactive situations where CO
detectors have alarmed or occupants have become ill from exposure. Many
institutions and organizations, such as the medical community, utility and fire
fighting groups, have CO standards for their use under specific situations. Often
these standards deal only with one portion of the home, or certain pieces of
equipment.
In order to enable accurate diagnosis of carbon
monoxide threats, the analysts must expand their view of a house and its
individual components. All of the systems of a building - HVAC, building shell,
occupant behavior - as well as outdoor conditions, act in an interrelated
fashion. CO Analysts must learn to look beyond specific sources of CO to
determine why a problem may begin, where one never existed before. Often, it
takes a number of circumstances happening concurrently in order for a hazard to
occur. The CO Analyst must learn how these systems interact, what sets of
circumstances may lead to CO entering a home, and a logical process for
investigating all of these factors when analyzing a building for CO.
The goal of this protocol is to provide a
standardized set of practices for HVAC contractors, utility personnel, fire
departments, home inspectors, and the building performance industry that will,
when implemented, lead to accurate diagnoses of potential or actual sources of
carbon monoxide within residences. These practices will be comprehensive in
nature, examining the interactions of all building systems within the home,
both with each other and with external conditions. This protocol will
facilitate implementing the proper treatment to alleviate potential and actual
exposure to CO by occupants of buildings through accurate, thorough, initial
inspections.
The Standards and Best Practices listed in this
document are non-fuel specific except where noted. They form the basis of the
CO Analyst Protocol. This protocol has been designed by the Carbon Monoxide
Safety Awareness Advisory Council and serves as a means of defining minimum
standards for the response industry. It must be realized that any government
agency or business entity may choose to uphold higher standards than the
protocol defines. Consistent with the Building Performance Institute's other
certifications, the protocol has been arranged into a format of standards and
best practices. These standards are intended to be reflective of a field-based
approach to doing work. BPI defines standard in this context as - to the extent
practical, the measurable goal of a set of best practices or procedures. Best practice
is defined as - by common agreement an action, activity, protocol or technique
that is the state of the practice. In other words, standards are what a worker
needs to do and best practices are how to do it.
Job Title:
Carbon Monoxide Analyst - This individual may be
self-employed or be employed by a utility, heating contractor, building
department, fire department, public health department, home inspection company,
equipment manufacturer/supplier or weatherization organization. Duties will include:
operation and maintenance of test equipment; conducting thorough visual
inspection of the building and combustion sources; ability to perform
comprehensive ambient CO analyses and perform CO tests on equipment found in a
typical building (vented heating appliance, domestic hot water, kitchen
range/oven, unvented heating appliances). Once tests are completed, the analyst
will interpret results, determine follow-up steps and perform occupant
education. This job designation is designed to serve as a mean competency for
responders from all sectors. It is not intended to serve as a mitigation
certification. This is a first step, front line certification for those
personnel who are first in the door answering a CO complaint or are responsible
for inspections ascertaining CO safety.
Carbon
Monoxide Analyst Test Equipment
Analysts shall have a digital CO
analyzer and a draft gauge to assist CO investigations. Differential pressure
manometers, blower doors and duct blasters are also useful in conducting these
investigations but are not required for personnel working at the CO Analyst
level.
Standard - CO Testing Instruments
- Carbon Monoxide test
instruments must meet the following minimum requirements.
- Digital display
capable of measuring 1 - 2 ppm increments @ 5 - 10% accuracy (COMMENT)
- Scale to read at
least up to 500 ppm.
- Reach 90% of final
reading within one minute.
- Have a probe/hose
assembly for flue gas sampling capable of withstanding high temperatures
and the ability to remove water vapor from the combustion by-products.
- Ability for
continuous sampling
Best Practices - CO Test Instruments
- CO test equipment can
be affected by heat, cold, humidity, battery strength and mishandling.
- Always warm up and
operate the instrument per manufacturer instructions.
Best Practices -Calibration of CO Testing
Equipment
- Instruments must be
calibrated per manufacturer instructions or when accuracy is in doubt.
- Field zeroing of the
instrument should only be done with test gases as described in the
owner's manual.
- Factory or other
certified calibration must be performed at recommended intervals. Do not
re-zero instruments for individual houses.
- Re-zeroing an
instrument without test gases may result in readings that are not
absolute or accurate.
- Zeroing of instruments
should never be attempted on a job. Temperature, battery level, truck
exhaust and other factors can affect zeroing.
- A constant need to
zero indicates an instrument or operator error.
- Zeroing an instrument
in the field eliminates reading the true ambient level.
Carbon
Monoxide Action Levels
Standard for Action Levels
The following action levels have been defined as minimums for BPI certified
Carbon Monoxide Analysts. Analysts may work for a government agency or business
entity that has adopted more stringent standards than the ones defined in this
document. As such, CO Analysts may enforce those higher standards. Under no
circumstances shall a BPI certified CO Analyst recognize less stringent
standards or ignore conditions in excess of the defined action levels. The
action levels are considered net indoor ambient readings - i.e. - indoor
ambient minus outdoor ambient readings.
0 to 9 parts per million (ppm)
Normal - No Action: Typical from: outdoor sources, fumes from attached garages,
heavy smoking, fireplace spillage and operation of unvented combustion
appliances. With ambient conditions in this range, analysts may continue
testing sequences.
10 to 35 parts per million (ppm)
Marginal: This level could become problematic in some situations. Actions:
Occupants should be advised of a potential health hazard to small children,
elderly people and persons suffering from respiratory or heart problems. If the
home has an attached garage, document CO levels in garage. Accept this level as
normal for unvented appliances but not for vented appliances. If unvented
appliances are in operation, recommend additional ventilation in the areas of
operation. With ambient conditions in this range, analysts may continue testing
to locate the CO source.
36 to 99 parts per million (ppm)
Excessive: Medical Alert. Conditions must be mitigated. Actions: Ask occupants
to step outside and query about health symptoms. Advise occupants to seek
medical attention. If occupants exhibit any symptoms of CO poisoning, have
someone drive them to a medical facility. Enter the building, open doors and
windows to ventilate the structure. Turn off all combustion appliances until
the CO level has been reduced to safe levels. If forced air equipment is
available, continuos operation of the air handler is recommended at this time.
If the home has an attached garage, document CO levels in garage. Test
combustion appliances one at a time to determine the source of CO production.
If an appliance is determined to be the source of CO production, it should be
shut off and not used until a qualified technician with proper test equipment
can service it.
100 - 200 parts per million (ppm)
Dangerous: Medical Alert. Emergency conditions exist. Actions: Evacuate the
building immediately and check occupants for health symptoms. Advise all
occupants to seek medical attention. Occupants should have someone else drive
them to a medical facility. If occupants exhibit symptoms of CO poisoning,
emergency service personnel must be called. Evacuation is important, but
Analysts must not subject themselves to excessive conditions. Maximum exposure
time is 15 minutes. Open all doors and windows that can be done quickly. If the
home has an attached garage, document CO levels in garage. Disable combustion
appliance operation. Continually monitor indoor ambient levels while moving
through the building. Once the atmosphere within the structure has returned to
safe levels and the appliances have been turned back on, locate the source of
CO production for corrective measures.
Greater than 200 parts per million (ppm)
Dangerous: Medical Alert. Emergency conditions exist. Actions: Evacuate the
building immediately and check occupants for health symptoms. Advise all
occupants to seek medical attention. Occupants should have someone else drive
them to medical facility. If occupants exhibit symptoms of CO poisoning,
emergency service personnel must be called. Evacuation is important, but
analysts must not subject themselves to these conditions. Do not stay inside or
re-enter the building until conditions have dropped below 100 ppm. Open all
doors and windows that can be done quickly without entering the structure. Call
the local utility to shut off gas supply (if applicable and necessary). If the
home has an attached garage, document CO levels in garage if possible to do so
without being subjected to high levels of CO. Once the atmosphere within the
structure has returned to safe levels, restore fuel supply to appliances.
Operate and test the appliances one at a time to determine the source of CO
production.
Classification
of CO Analyses
Standard - Classification of CO Analyses
Inspections conducted by BPI certified CO Analysts must be classified either
routine or priority. This will be determined by conditions prompting the request
for a CO inspection. For CO Analyses conducted as a part of heating system
maintenance, these analyses shall be considered routine unless the customer
exhibits or complains of CO symptoms. Classification of CO inspections
resulting from a customer request will be determined by information provided by
the customer at the time of initial contact, preferably over the phone. This is
done to ensure an adequate response in situations where a customer's health may
be endangered. Conduct a short interview to adequately determine the
prioritization of the CO inspection request.
Best Practices - CO Inspection Classification
- All customers
reporting they or someone in the home may have symptoms of CO poisoning
will be treated as a priority.
- Customers requesting
a routine safety inspection shall be queried for manifestations of CO
poisoning symptoms. The call must be treated as a priority if the caller
reports symptoms, otherwise it may be classified as a routine inspection.
- Customers requesting
an inspection due to a CO detector alarm will be classified as a
priority.
- Anytime a customer
reports evidence of potential CO poisoning symptoms, advise them to
vacate the premises and wait outside or next door for the inspector.
- Any requests
receiving priority status must be immediately responded to. If immediate
response is not possible, notify another certified analyst or contact
utility/emergency response personnel.
- Requests classified
as routine may be scheduled accordingly.
CO
Inspection Protocol
Standard CO Inspection
A comprehensive protocol will be adhered to by BPI certified CO Analysts. This
protocol includes: Ambient CO Level Testing, Client Interview, Building
Inspection, Equipment Testing, Detector Utilization and Customer Education.
Standard - CO Testing, Ambient Levels
Accepted CO protocol should be followed, upon request of testing, whenever CO
contamination is suspected, and when combustion appliances are serviced.
Ambient levels will be tested before and after any work is done. All readings
will be recorded. Ambient tests must be performed prior to conducting the
client interview and/or inspections of the dwelling.
Best Practices - Measuring Ambient CO Levels
- Ensure your
instrument has been "warmed up" per manufacturer instructions.
- Measure actual
outdoor ambient CO away from any potential source; auto, sidewall vented
appliances, etc.
- Record outdoor
reading as a baseline reference point.
- Proceed into the
building entrance for an initial indoor CO ambient reading.
- Subtract outdoor reading
from any indoor reading to determine the magnitude of any CO problem
found within the home.
- Record the results
found at the entrance, just inside the building.
- Determine if
atmosphere is safe for continued testing. See action levels.
- If action levels
dictate a response follow Standard for Action Levels. If conditions are
deemed safe, proceed with customer interview.
Standard - Occupant Interview
An interview with the building occupant(s) is an essential component of all CO
testing. The occupants may describe when they have problems and/or what they
think might be causing it. A history of health symptoms and possible CO
occurrences may help to pinpoint any potential problems. CO Analysts shall
conduct an occupant interview as a part of every inspection.
Best Practices - Client Interview
- Perform interview in
an area safe from CO exposure.
- Inquire about health
problems.
- Question occupants to
see if they have experienced any specific CO poisoning symptoms
including: headaches, dizziness, nausea, confusion, rapid breathing,
fatigue, unconsciousness, disorientation, or flue like symptoms.
- Ask if anyone else in
the home has shown signs of experiencing these symptoms.
- If anyone appears to
be experiencing symptoms, refer them to medical evaluation (see action
levels).
- Ask about unusual
moisture problems.
- Ask about recent
mechanical problems.
- Ask if a vehicle has
been in or out of the garage recently (if applicable).
- Ask if oven or range
was in use. Ask if the fireplace was in use (if applicable).
- Ask if occupants were
doing laundry or vent fans were in use.
- Repeat customer
health inquiries if a serious CO problem is found and the occupants have
not acknowledged any symptoms previously.
- Reference action
levels.
Standard - Building Inspection
A walk through inspection of the structure is necessary to ensure no potential
source of CO production is missed. Utilize a standardized recording form to
ensure no potential source is missed and document all findings for future
reference.
Best Practices - CO Recording Form
Use a standardized CO recording form when performing a CO inspection. Include:
- Company, technician,
date and time of testing.
- Client and physical
location.
- Interview information
including health symptoms.
- Smokers in the
structure.
- Is this an emergency
situation or routine procedure - inspection classification.
- Listing of normal CO
sources to be inspected and results from testing those sources.
- Location of all
Combustion Appliance Zones.
- Mechanical and
passive ventilation within the structure.
- Type of fuels in use.
- Location and numbers
of smoke and CO detectors.
- Make, model numbers
and type of detectors.
- Attached or detached
garage.
- Potential exterior
sources of CO production.
- Type, model and
serial numbers of combustion appliances.
- Vent system condition
for each appliance (if vented).
- Weather conditions of
the day.
- Action taken.
- Follow-up
Best Practices - Building Walk Through
Inspection
- Record all testing
information.
- Continually test for
ambient CO levels while inspecting each zone.
- Note any CO readings
in attached garages.
- Inspect for and
record any CO sources near exterior of house (busy street, grills,
go-carts, shop with gasoline, power equipment, etc.)
- Identify and inspect
each Combustion Appliance Zone (CAZ) within the building recording number
and type of combustion appliances.
- Inspect for and
record in each CAZ: the number, type and location of exhaust appliances
(bathroom vent fans, kitchen range hoods, dryers, exhausting cook tops).
Best Practices - Combustion Appliance Zone
(CAZ)
- Specific attention
must be paid to CAZ's as these are likely sources of CO production.
- Identify and record
location of all CAZ's. Include vented appliances and unvented appliances.
- Inspect venting
systems. Note corrosion and flue gas spillage. Inspect flue pipe and
where it joins chimney for leakage.
- Questions concerning
venting can be checked against manufacturer literature or the following
codes: NFPA 211 (solid fuel); NFPA 31 (oil); or NFPA 54 (gas).
Standard - Appliance Testing
All combustion appliances will be tested individually for CO production. If
operation of any appliance raises ambient CO concentrations in the dwelling
above 35 ppm, the appliance must not be operated by the homeowner until the
cause is corrected.
Best Practices - House Preparation
Prior to testing combustion appliances, the house must be set to winter mode.
- Windows closed.
- Exterior doors
closed.
- Close equipment room
doors.
- Turn off all
combustion appliances.
Best Practices - General Procedure for
Appliance Testing
- Test vented
combustion appliances first.
- Test unvented
appliances only after completing vented appliance tests.
- Test common vented
appliances individually beginning with the smaller appliance.
- If both appliances
pass then test while both are firing.
- Test ambient air in
the combustion appliance zone before testing combustion gases.
- Always monitor
ambient CO levels to ensure health and safety.
- When ambient levels
(space levels) within the CAZ are:
- 0 - 9 ppm
Okay to test.
- 10 - 35 ppm
Proceed with testing but carefully monitor ambient.
- 36 - 99 ppm
Turn appliance off and ventilate area. When ambient CO levels are
reduced to safe levels, operate one appliance at a time until source is
located. Disable the defective appliance until it can be repaired.
- Greater than
100 ppm Stop testing, shut down the appliance(s), ventilate the
area and exit the building. When ambient CO levels are reduced to safe
levels, operate one appliance at a time until source is located. Disable
the defective appliance until it can be repaired.
- Perform draft tests
for all vented combustion appliances creating worst case conditions.
- Once each combustion
appliance has been tested individually for CO, retest the appliances
while all are in operation.
Best Practices - Furnace CO Testing
- Test oil fired
furnaces in the vent connector before the barometric damper.
- Test low efficiency
propane and natural gas furnaces (<80%) at the outlet of each heat
exchanger section before the draft diverter or collector box, and before
any dilution air. Treat drum type heat exchangers as one cell.
- Test mid (80%) and
high (90%) efficiency propane and natural gas furnaces in the vent connector
after the draft inducer. Drill a hole in the vent pipe 12" to
18" above the outlet thimble. This hole must be sealed after testing
is complete.
- CO readings should
peak, drop, then stabilize within 5 minutes. If CO readings continue to
climb for more than five minutes the condition must be considered unsafe
and corrected - even if CO levels are still below 100 ppm.
- If highest single CO
readings are:
- 0 - 99 ppm
conditions are acceptable.
- 100 - 200 ppm
at any location, the condition must be considered unsafe and the problem
corrected. The unit may be operated minimally if no spillage of flue gas
is detected.
- 200 - 400 ppm
at any location, the condition must be considered unsafe and the problem
corrected immediately. The unit may be operated minimally if no spillage
of flue gas is detected.
- Greater than
400 ppm Conditions are considered unsafe. The appliance must be
disabled and not run (even if no CO is detected in the ambient space)
until the condition is corrected.
- Readings in all cells
of the heat exchanger should be taken several times over a five minute
period to verify stability.
- After the initial CO
test on the furnace, any additional appliances venting air from the
structure should be turned on one at a time to see if they affect operation.
Continuous readings on the furnace should show no change in CO readings.
Do not perform this stress test on units producing CO greater than 200
ppm, however conduct draft test.
- During this test ,
perform a draft test on the furnace. Draft gauge probe should be inserted
above the draft hood or diverter. Normal draft is between .01" and
.02" W.C.
- Any draft below
.01"WC is a potential draft problem.
- Additional doors
should be opened or closed at this time to see if their position has any
affect on draft.
- Any reduction in
draft when other appliances are turned on indicates a problem even if no
carbon monoxide is measured. Undersized flue pipe, restricted chimney or
negative pressure in the CAZ is indicated.
- Any vented appliance
spilling CO should be not be operated until the problem is corrected.
- Visual signs of rust
and black or white soot on the appliance cabinet or inside the vestibule
may indicate unsafe operation even if no elevated CO readings are found
in the CO testing sequence.
Best Practices - Furnace Burner Light-off and
Peak Test (Propane and Natural Gas only)
- A light-off test
should be taken after one cycle at the farthest burner from the pilot.
- CO readings that peak
above 400 ppm at this point can indicate pilot, igniter, or burner problems.
- Fire the unit,
observe for peak CO.
- When the appliance
shuts off from the light off test, testing should continue in one heat
exchanger cell for a period of 60 seconds.
- Increase of CO
readings following shut down may indicate a leaky fuel valve or pump.
Best Practices - Boiler CO Testing
- Test oil fired
boilers in the vent connector before the barometric damper.
- Test low efficiency
propane and natural gas boilers (<80%) at the outlet of each heat
exchanger section before the draft diverter or collector box, and before
any dilution air.
- Test mid (80%) and
high (90%) efficiency propane and natural gas boilers in the vent
connector after the draft inducer. Drill a hole in the vent pipe 12"
to 18" above the outlet thimble. This hole must be sealed after
testing is complete.
- CO readings should
peak, drop, then stabilize within 5 minutes. If CO readings continue to
climb for more than five minutes the condition must be considered unsafe
and corrected - even if CO levels are still below 100 ppm.
- If highest single CO
readings are:
- 0 - 99 ppm
conditions are acceptable
- 100 - 200 ppm
at any location, the condition must be considered unsafe and the problem
corrected. The unit may be operated minimally if no spillage of flue gas
is detected.
- 200 - 400 ppm
at any location, the condition must be considered unsafe and the problem
corrected immediately. The unit may be operated minimally if no spillage
of flue gas is detected.
- Greater than
400 ppm Conditions are considered unsafe. The appliance must be
disabled and not run (even if no CO is detected in the ambient space)
until the condition is corrected.
- Readings in all cells
of the heat exchanger should be taken several times over a five minute
period to verify stability.
- After the initial CO
test on the furnace, any additional appliances venting air from the
structure should be turned on one at a time to see if they affect
operation. Continuous readings on the furnace should show no change in CO
readings. Do not perform this stress test on units producing CO greater
than 200 ppm, however conduct draft test.
- During this test ,
perform a draft test on the furnace. Draft gauge probe should be inserted
above the draft hood or diverter. Normal draft is between .01" and
.02" W.C.
- Any draft below
.01"WC is a potential draft problem.
- Additional doors
should be opened or closed at this time to see if their position has any
affect on draft.
- Any reduction in
draft when other appliances are turned on indicates a problem even if no
carbon monoxide is measured. Undersized flue pipe, restricted chimney or
negative pressure in the CAZ is indicated.
- Any vented appliance
spilling CO should be not be operated until the problem is corrected.
- Visual signs of rust
and black or white soot on the appliance cabinet or inside the vestibule
may indicate unsafe operation even if no elevated CO readings are found
in the CO testing sequence.
Best Practices - Boiler Burner Light-off and
Peak Test (Propane and Natural Gas only)
- A light-off test
should be taken after one cycle at the farthest burner from the pilot.
- CO readings that peak
above 400 ppm at this point can indicate pilot, igniter, or burner
problems.
- Fire the unit,
observe for peak CO.
- When the appliance
shuts off from the light off test, testing should continue in one heat
exchanger cell for a period of 60 seconds.
- Increase of CO
readings following shut down may indicate a leaky fuel valve or pump.
Best Practices - Domestic Hot Water Tank CO
Testing
- Initially test DHW
tank with no other appliances or exhaust operating.
- Test Oil fired DHW
tanks in the flue before the barometric damper.
- Test Propane or Gas
fired tanks in the fire tube on both sides of the baffle.
- CO readings should
peak, drop, then stabilize within 5 minutes. If CO readings continue to
climb for more than five minutes the condition must be considered unsafe
and corrected - even if CO levels are still below 100 ppm.
- If highest single CO
readings are:
- 0 - 99 ppm
conditions are acceptable
- 100 - 200 ppm
at any location, the condition must be considered unsafe and the problem
corrected. The unit may be operated minimally if no spillage of flue gas
is detected.
- 200 - 400 ppm
at any location, the condition must be considered unsafe and the problem
corrected immediately. The unit may be operated minimally if no spillage
of flue gas is detected.
- Greater than
400 ppm Conditions are considered unsafe. The appliance must be
disabled and not run (even if no CO is detected in the ambient space)
until the condition is corrected.
- Readings in all cells
of the heat exchanger should be taken several times over a five minute
period to verify stability.
- After the initial CO
test, any additional appliances venting air from the structure should be
turned on one at a time to see if they affect operation. Continuous
readings should show no change in CO readings. Do not perform this stress
test on units producing CO greater than 200 ppm, however conduct draft
test.
- During this test ,
perform a draft test. Draft gauge probe should be inserted above the
draft hood or diverter. Normal draft is between .01" and .02"
W.C.
- Any draft below
.01"WC is a potential draft problem.
- Additional doors
should be opened or closed at this time to see if their position has any
affect on draft.
- Any reduction in
draft when other appliances are turned on indicates a problem even if no
carbon monoxide is measured. Undersized flue pipe, restricted chimney or
negative pressure in the CAZ is indicated.
- Any vented appliance
spilling CO should be not be operated until the problem is corrected.
- Visual signs of rust
and black or white soot on the appliance cabinet or inside the vestibule
may indicate unsafe operation even if no elevated CO readings are found in
the CO testing sequence.
Best Practices - Other Vented Appliances
- Types of appliances
such as Space Heaters, Gas Dryers, Gas Fireplaces, Vented Ovens/Ranges.
- These units must be
properly vented in accordance with applicable codes.
- Repeat steps from Furnace
CO Test Best Practices.
Best Practices - Unvented Appliances - Space
Heaters, Gas Fireplaces +
- Should be tested
after vented appliance testing is completed.
- Do not leave the CAZ
while testing is in progress.
- Test unvented
appliances 6 inches above the flame, or insert the instrument probe into
the vent sleeve before dilution air has an opportunity to be mixed in
with flue gases.
- Less than 50
ppm after 2 - 3 minutes of operation - OK
- 50 - 99 ppm
after 2 - 3 minutes of operation - Marginal. Have the appliance serviced
- Greater than
100 ppm after 2 - 3 minutes - Unsafe. The appliance should not be
used until repaired.
Best Practices - Ranges and Ovens
Ovens
- Should be tested
after vented appliance testing is completed.
- Do not leave the CAZ
while testing is in progress.
- For oven tests,
remove any items stored in the oven before proceeding.
- Remove foil coverings
from broil areas.
- Make sure that
self-cleaning features are not activated. This may produce excessive
levels of CO.
- Test ovens by inserting
the instrument probe into the vent sleeve before dilution air mixes with
combustion by-products.
- Continually test
ovens during warm up and record peak. (10 minutes)
- CO levels greater
than 400 ppm during warm up or levels that stay high for several minutes
before decreasing indicate potential problems and should be serviced or
replaced.
- For units with
separate broiler burner, repeat test.
- Continually monitor
ambient space around oven during testing.
- Note: Electric
ovens with excessive buildup or in self cleaning mode may produce carbon
monoxide.
Range Top
- Test after vented
appliance testing is completed.
- Do not leave the CAZ
while testing is in progress.
- Remove all pots and
foil from the burner area.
- Turn all range top
burners on high and allow to warm.
- Test 6" above
the flame without pots or test fixtures.
- When an unvented
stove/range is found in a building, stress the need for a strategy to
vent pollutants to the outdoor atmosphere.
- Less than 50 ppm
after 2 - 3 minutes of operation - OK
- 50 - 99 ppm
after 2 - 3 minutes of operation - Marginal. Have the appliance serviced
- Greater than
100 ppm after 2 - 3 minutes - Unsafe. The appliance should not be
used until repaired.
Best Practices - Wood Burning Appliances
- Wood appliances
always produce high levels of CO during operation. No flue gas spillage
must occur.
- Continually test
ambient CO levels with normal household appliances operating; exhaust
vents, air handler blower on, heating appliance operating, clothes dryer,
etc.
- Perform a draft test
on the wood flue for vented appliances if they are in operation.
- Ensure no spillage
occurs from fireplaces through the operation furnace blowers, range vents
dryers and exhaust fans.
- Note proximity of
furnace cold air returns to fireplace.
- Test fireplaces for
CO above hearth near the wall. This is an ideal spot for CO detector.
Standard - Retest Ambient
After completion of appliance CO testing, ambient CO tests in all zones should
be re-tested to ensure no change in CO from initial tests.
Standard - CO Detectors
Upon completion of a CO analysis, check all CO detectors in the home to ensure
proper maintenance and operation. Analysts should recommend CO detector
installation near bedrooms and in all CAZ's. Detectors that provide warnings
between 35 - 99 ppm are recommended - especially if small children, elderly or
persons with health problems occupy the building. Detectors that maintain
operation during power outages ( battery powered or battery back-up) provide
additional safety. Detectors should have the capability of being mounted at eye
level or higher. Digital detectors can provide the earliest warning, but only
when visually observed. Detectors should meet current standards, UL2034 or IAS
6-96 (subject to change). Installing one battery detector near sleeping areas
and one digital detector in living areas where it can be easily observed is an
excellent protection strategy.
Best Practices - CO Detectors
- Follow detector
manufacturer's recommendations for installation and maintenance.
- If only one detector
is installed, it should be located near the bedrooms, mounted high in an
area of good airflow.
- Install CO detectors
in all combustion appliance zones (CAZs)
- Areas containing
unvented combustion appliances and those with wood burning stoves or
fireplaces should have a digital CO detector.
Standard - Client Education
CO Analysts shall work with the occupants requesting the analysis to inform
them about: the test results on their house, potential sources of CO in homes,
causes of CO production, how to minimize risk of CO poisoning, proper
maintenance of HVAC equipment and detector placement/maintenance.
Best Practices - Client Education
- Thoroughly review the
results of the CO analysis with the customer. Explain to them you are
going to discuss sources of CO, causes for its production and then
develop a protection strategy for their home.
- Discuss with the
customer all potential sources of CO production. Include the following:
outside sources such as roads; automobiles in attached garages; other
gasoline powered equipment such as generators; indoor combustion
appliances such as heating systems, DHW heaters, kitchen ranges; gas or
wood fired fireplaces; self cleaning ovens; and unvented space heaters.
- Inform the occupants
about the causes of CO production. Include: normal by-product from
internal combustion engines, incomplete combustion, insufficient air,
lack of maintenance, improper equipment set-up and impingement restricting
the combustion process.
- Discuss strategies to
minimize risk of CO build-up in the home. Include: never warming up car
in garage, providing ventilation where fireplaces/unvented space heaters
are in use, vent use for kitchen range and annual servicing of combustion
appliances by trained professionals knowledgeable in the use of CO
testing equipment.
- Develop in
conjunction with the customer a protection strategy for their home which
shall include: maintenance schedules for appliances including occupant performed
tasks such as filter changing, adequate CO detector coverage and
maintenance of detectors, operation of ventilation systems, and
use/operation of fireplaces/unvented space heaters.